Model Number: HL-HLD06
Brand Name: HOLLEY INTL
Key Specifications/Special Features:
Construction:Meter case: socket type meter case complies with ANSI C 12.7-1993 and meets protection requirements set by ANSI C 12.10-1993Driving element:Rotor:Upper bearing: consists of guide pin and aluminum sleeveLower bearing: consists of guide pin and brass sleeve and fixed into meter frame by one screw
Braking element:
Consists of voltage element and current element, both of which are fixed on aluminum alloy frame
Load curve compensation mechanism and inductive load adjustment mechanism
Worm un-detachable part of shaft so that mesh between worm and shaft improved
Both ends of shaft are embedded with graphite bearing to ensure long service lifespan of meter
Two magnet cubes are die-casted into meter frame by aluminum alloy
Temperature compensation plate
Frame die-casted by sial alloy of stable property to avoid distortion
Low load adjustment mechanism
Technical data:
- Frame:
- Register: both pointer and cyclometer registers
- Applicable standards: ANSI C 12.1 and ANSI C 12.10
- Class: 10, 20, 100 and 200
- Test current: 2.5, 15 and 30A
- Meter constant: 1400, 1200, 360 and 90r/kWh
- Average service lifespan: 30 years
- Overload capacity: 667%
- Heat capacity: Ib+imax
- Short time over current: 7000A, short circuit 0.1s
- Reference voltage: 110, 120, 220, 230, 240, 277 and 480V
- Reference frequency: 60Hz
- Non-running with no-load: 0.9 to 1.1Un
- Starting current: 1% ib
- Rated load speed at ib: 11rpm
- Power losses in voltage circuit at 60Hz un: less than 1W/5VA
- Power losses in current circuit at ib: less than 0.5VAAC voltage test at 60Hz, 1 min: 2.5kV
- Impulse voltage test at 1.2/50ms: >6.5kV
- Rated load torque at unity PF, IB: 400UnM
- Weight of rotor: 26g
- Weight of meter: 1.7kg (approximately)
Shipping Information:
- FOB Port: Shanghai
- Lead Time: 15 - 30 days
Main Export Markets:
- Asia
- Central/South America
- Eastern Europe
- Mid East/Africa
- North America
- Western Europe